Tag: oil treatment

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2012

Scenario Hydro power plant with 3 GSU transformers Nameplate data of the transformer: Manufact: xxx Year: 1965 Power [MVA]: 80 Voltage [KV]: 220 Oil mass [Kg]: 35.000 Oil type: naphthenic blended Solution Selective deplarization treatment (Chedcos) in order to remove the corrosive sulfur compounds and dehalogenation treatments (CDP Process®) in order to remove the PCBs from the oil and the transformers. the tratments were performed
Read more

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2010

Scenario Steel Factory: 8 Equipment Nameplate data of the transformers: Namufact: xxx Year: 1973 Power [MVA]: 85 Voltage [KV]: 63 Oil mass [Kg]: 18.150 Oil type: naphthenic blended Oil Fingerprint. It shows the presence of sulfur compounds responsible for oil corrosivity Solution Selective depolarization treatment (Chedcos) in order to remove the corrosive sulfur compounds and dehalogenation treatments (CDP Process®) in order to remove the PCBs from the oils
Read more

Francia 2012 Rimozione zolfo corrosivo senza DBDS (C2)

Scenario Il classico trattamento con terre follari si dimostra totalmente inefficace contro lo zolfo corrosivo Caratteristiche tecniche del trasformatore: Costruttore: xxx Anno: 1969 Potenza [MVA]: 14 Tensione [KV]: 63 Massa olio [Kg]: 4.200 Tipo di olio: Esso Univol 54 Oil Fingerprint. Presence of sulfur compounds without DBDS Il trattamento con terre follari (NON da Sea Marconi) non ha prodotto alcun risultato
Read more

Removal of non-DBDS corrosive sulfur (C2) Midlle East 2009

Scenario Thermal power plant with 8 GSU transformers Nameplate data of the transformers: Power [MVA]: 175 Voltage [KV]: 400 Oil type: naphthenic oil C2 – Corrosion not caused by DBDS Step 1 The diagnosis in the 2009 showed: Total sulfur = 200 mg/Kg TCS (Total Corrosive Sulfur) = 157 mg/Kg (DBDS eq.) CCD Test = corrosive IFT = 19 mN/m DBTP
Read more

Removal of corrosive sulfur with DBDS C1 Qatar 2012

Scenario Company in the chemical business, 4 GSU transformer Nameplate data of the transformer: Manufatc: xxx Year: 2000 Power [MVA]: 47 Voltage [KV]: 34 Oil mass [Kg]: 12.000 Oil type: naftenico Solution Solution: Selective depolarization treatment (Chedcos) performed on-ste and on-load (transformer in service e fully load during the treatment). The treatment has guaranteed DBDS < 10 mg/kg. Before treatment After treatment DBDS [mg/Kg] 125
Read more

Removal of corrosive sulfur with DBDS (C1) Chile 2012

Scenario Primary substation with 3 Grid transformer and 2 shunt reactors Nameplate data of the transformer: Manufact: xxx Year: 1998 Power [MVA]: 250 Voltage [KV]: 345 Oil mass [Kg]: 118.000 Oil type: naphthenic Analitical and diagnostic results The analysis and subsequent diagnosis performed by Sea Marconi on the machines of the customer showed a clear presence of DBDS Distillation profile of
Read more

Removal of corrosive sulfur with DBDS (C1) Italy 2005

Scenario 4 GSU transformer at thermal power plant Nameplate data of the transformers: Manufact: xxx Year: 1997 Power [MVA]: 192 Voltage [KV]: 400 Oil mass [Kg]: 58.000 Oil type: naphthenic May 2005 The analysis and subsequent diagnosis performed by Sea Marconi on the equipment of the customer showed: Index of corrosiveness =1 (max level) ASTM b 48H= 4C Overall Health index: 0.52
Read more

Removal of corrosive sulfur with DBDS (C1) Italy 2009-2014

Scenario Company involved in energy transmission (36 transformers) Nameplate data of transformers: Power max [MVA]: 528 Voltage max [KV]: 400 Oil mass [Kg]: 96.900 each DBDS max [mg/Kg]: 185 DBDS target [mg/Kg]: <5 2009-2013 Solution: Selective depolarization treatments by Sea Marconi in order to remove corrosive sulfur compounds from the oils.
16
Apr
2013

Insulating oil treatments: “Sea Marconi Solution” vs “Fuller Earth treatments”

Benchmarking between the different techniques of oil treatment during the life cycle of oils and transformers Download the flier PDF: Sea Marconi Treatments Vs Fuller Earth treatments ENG (377.5 KiB) Key Factors DMU & Integrated Treatments* Sea Marconi Patented Treatment with typical Fuller Earth Treatment with typical Fuller Earth and regeneration > 600-700 °C Recovery: Physical Properties KV, DGA, H2O  Yes
Read more
29
Nov
2012

Sustainable PCBs-free solutions in Macedonia; inaugurated the Sea Marconi plant

On 7th November 2012. at the specialised centre organised by the company RADE KONCAR in Skopje (Macedonia), the plant developed by Sea Marconi for the decontamination and recovery of oils and transformer contaminated by PCBs (Polychlorinated biphenyls) has been inaugurated. The project for the “environmental protection through the reduction and the elimination of dangerous substances such as PCBs in the oil of transformers”