Tag: PCB

PCBs and C2 and C4 corrosion, extreme logistics France 2013

Scenario Hydro Power Plant The transformer is located near a river dam with extreme logistical and environmental constraints. The option of changing the oil was discarded immediately because of the enormous difficulties in handling (see. Photo) around the transformer. At the same time the fuller earth techniques would not solve the functional criticalities of the system “oil – transformer”. Nameplate
Read more
20
Feb
2014

Mexico, Sea Marconi is ready for the Environmentally Sound Management and Destruction of PCBs

For Sea Marconi 2013 ended with very interesting outlooks; one of these involves the opportunity offered by Mexico, engaged in the project for the destruction of PCBs: Environmentally Sound Management and Destruction of PCBs in Mexico. The project, started in 2009, involves the joint effort by the Ministry of Environment and natural resources (SEMARNAT), the Ministry of Foreign Affairs, UNDP (United Nations
Read more

Removal of PCBs and environmental protection France 2012

Scenario Nameplate data of transformer: Trasformatore: grid transformer Manufact: xxx Year: 1970 Power [MVA]: 70 Voltage [KV]: 225 Oil mass [Kg]: 38.000 Solution Sea Marconi Dealogenazione (CDP Process®) treatment in order to remove the PCBs, performed on-load (this means that the transformer is in service and under load during the treatment) Trend of PCBs and chlorine content during the dehalogenation treatment (CDP Process)
Read more

Removal of PCBs and environmental protection France 2008

Scenario Nameplate data of transformer: Transformer: GSU transformer Manufact: xxx Year: 1974 Power [MVA]: 760 Voltage [KV]: 400 Oil mass [Kg]: 55.000 Problem See analytical results of the oil before treatment (table below) Soluzione Sea Marconi Solution: Dehalogenation treatment (CDP Process®) in order to remove the PCBs from the oil and transformer. Before treatment After treatment TAN [mg KOH/g] 0,029 < 0,010 Breakdown
Read more

Removal of PCBs and environmental protection France 2004-2012

Scenario Utility – Power transformer of generation (nuclear, thermal, hydro), transmission and distribution with a total of 1.093 transformers. Namepale data of transformers: Power max [MVA]: 760 Voltage max [KV]: 400 Oil mass [Kg]: 75.000 each PCB max [mg/Kg]: 5.000 PCB target [mg/Kg]: < 20 (after 90 days) Solution Sea Marconi Solution: Dehalogenation treatment (CDP Process®) in order to remove the PCBs from oils and transformers. The treatments
Read more

Removal of PCBs and environmental protection Cyprus 1997

Scenario International Tender of the Electricity Authority of Cyprus for: “Elimination of PCBs from the insulating oil of distribution transformers”. In the 1997 Sea Marconi awarded the tender for decontaminate 520 transformers. Nameplate data of transformers: Power max [KVA]: 10-1000 Oil mass contaminated [Kg]: 94.000 PCB max [mg/Kg]: 15.000 PCB target [mg/Kg]: < 10 Solution Sea Marconi Solution: Dehalogenation treatment (CDP Process®) in order to remove
Read more

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2013

Scenario Nameplate data of transformer: Transformer: grid transformer Manufact: xxx Year: 1957 Power [MVA]: 50 Voltage [KV]: 225 Oil Mass [Kg]: 38.000 Oil type: blended mineral oil Transformer contaminated by PCBs and corrosive sulfur compounds Solution Selective depolarization treatment (Chedcos) in order to remove corrosive sulfur compounds and dehalogenation treatment (CDP Process®) in order to remove the PCBs from oil and transformer. The treatment was performerd on-site
Read more

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2012

Scenario Hydro power plant with 3 GSU transformers Nameplate data of the transformer: Manufact: xxx Year: 1965 Power [MVA]: 80 Voltage [KV]: 220 Oil mass [Kg]: 35.000 Oil type: naphthenic blended Solution Selective deplarization treatment (Chedcos) in order to remove the corrosive sulfur compounds and dehalogenation treatments (CDP Process®) in order to remove the PCBs from the oil and the transformers. the tratments were performed
Read more

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2010

Scenario Steel Factory: 8 Equipment Nameplate data of the transformers: Namufact: xxx Year: 1973 Power [MVA]: 85 Voltage [KV]: 63 Oil mass [Kg]: 18.150 Oil type: naphthenic blended Oil Fingerprint. It shows the presence of sulfur compounds responsible for oil corrosivity Solution Selective depolarization treatment (Chedcos) in order to remove the corrosive sulfur compounds and dehalogenation treatments (CDP Process®) in order to remove the PCBs from the oils
Read more
31
May
2013

Sea Marconi Latinoamericana, 10 years of successes aiming at 2028

Sea Marconi Latinoamericana sa was born in 2004 to provide core business services to several customers on the Argentine market, among them some primary utilities and industrial groups, such as Esso, Siderca Tenaris Group, etc.Since its foundation the Latin American company Sea Marconi was engaged to stay permanently in that market with a system for the treatment of oils and transformers
Read more