The treatment of corrosive sulfur on giant transformers in Saudi Arabia is now in Transformer Magazine

The technical-scientific article describing the corrosive sulfur depolarization treatment (DBDS removal) on giant transformers that Sea Marconi is carrying out in Saudi Arabia has seen the publication (October 2022) in the main sector magazine, Transformer Magazine. The article is entitled: "On-load integrated treatment of giant power transformers in a severe scenario". The article, subjected to careful technical review by Transformer
Leia mais
11
Ago
2015

EDP Portugal qualifies Sea Marconi thanks to its corrosive sulphur treatment

Sea Marconi recently intervened to treat a transformer in a hydro-electric production plant in the north of Portugal, owned by EDP (Energias de Portugal), one of the largest producers of energy in Europe and one of the most important industrial groups in Portugal. The brilliant results of this activity earned Sea Marconi formal qualification by EDP (Labelec) for the “regeneration” of insulating oil in
Leia mais

Remoção de enxofre corrosivo com DBDS (C1) – Região do Pacífico 2012

Scenario Company involved in production of primary aluminum with 8 rectifiers transformers Nameplate data of the transformers: Transformer: rectifier, ODAF with membrane Manufact: xxx Year: 1998 Power [MVA]: 93,4 Voltage [KV]: 66 Oil mass [Kg]: 27.200 Oil type: naphthenic Step 1 First failure with discharges of high energy (D2) Step 2 Post failure analysis, oil fingerprint with identification ant quantification of
Leia mais

Remoção de enxofre corrosivo com DBDS (C1) – Qatar 2012

Scenario Company in the chemical business, 4 GSU transformer Nameplate data of the transformer: Manufatc: xxx Year: 2000 Power [MVA]: 47 Voltage [KV]: 34 Oil mass [Kg]: 12.000 Oil type: naftenico Solution Solution: Selective depolarization treatment (Chedcos) performed on-ste and on-load (transformer in service e fully load during the treatment). The treatment has guaranteed DBDS < 10 mg/kg. Before treatment After treatment DBDS [mg/Kg] 125
Leia mais

Remoção de enxofre corrosivo com DBDS (C1) – Chile 2012

Scenario Primary substation with 3 Grid transformer and 2 shunt reactors Nameplate data of the transformer: Manufact: xxx Year: 1998 Power [MVA]: 250 Voltage [KV]: 345 Oil mass [Kg]: 118.000 Oil type: naphthenic Analitical and diagnostic results The analysis and subsequent diagnosis performed by Sea Marconi on the machines of the customer showed a clear presence of DBDS Profilo di distillazione
Leia mais

Remoção de enxofre corrosivo com DBDS (C1) – Itália 2005

Scenario 4 GSU transformer at thermal power plant Nameplate data of the transformers: Manufact: xxx Year: 1997 Power [MVA]: 192 Voltage [KV]: 400 Oil mass [Kg]: 58.000 Oil type: naphthenic May 2005 The analysis and subsequent diagnosis performed by Sea Marconi on the equipment of the customer showed: Index of corrosiveness =1 (max level) ASTM b 48H= 4C Overall Health index: 0.52
Leia mais

Remoção de enxofre corrosivo com DBDS (C1) – Itália 2009-2014

Scenario Company involved in energy transmission (36 transformers) Nameplate data of transformers: Power max [MVA]: 528 Voltage max [KV]: 400 Oil mass [Kg]: 96.900 each DBDS max [mg/Kg]: 185 DBDS target [mg/Kg]: <5 2009-2013 Solution: Selective depolarization treatments by Sea Marconi in order to remove corrosive sulfur compounds from the oils.

Remoção de enxofre corrosivo com DBDS (C1) – Brazil 2005

Scenario Brazilian energy transmission network of TSN e Novatrans with 76 electrical equipment filled with insulating fluids. Sistema di trasmissione Brasile TSN Lines 1181 km Substations 6 Total reactors 40 Reactors with corrosive sulfur 37 (92,5%) Total failed reactors 15 (37,5%) Novatrans Lines 1278 km Substations 6 Total reactors 36 Reactors with corrosive sulfur 13 (36,11%) Total failed reactors (-) 2005 Discovery of DBDS. Sea Marconi, first in the
Leia mais