Remoção de enxofre corrosivo com DBDS (C1) – Itália 2005

Scenario 4 GSU transformer at thermal power plant Nameplate data of the transformers: Manufact: xxx Year: 1997 Power [MVA]: 192 Voltage [KV]: 400 Oil mass [Kg]: 58.000 Oil type: naphthenic May 2005 The analysis and subsequent diagnosis performed by Sea Marconi on the equipment of the customer showed: Index of corrosiveness =1 (max level) ASTM b 48H= 4C Overall Health index: 0.52
Leia mais

Remoção de enxofre corrosivo com DBDS (C1) – Itália 2009-2014

Scenario Company involved in energy transmission (36 transformers) Nameplate data of transformers: Power max [MVA]: 528 Voltage max [KV]: 400 Oil mass [Kg]: 96.900 each DBDS max [mg/Kg]: 185 DBDS target [mg/Kg]: <5 2009-2013 Solution: Selective depolarization treatments by Sea Marconi in order to remove corrosive sulfur compounds from the oils.

Remoção de enxofre corrosivo com DBDS (C1) – Brazil 2005

Scenario Brazilian energy transmission network of TSN e Novatrans with 76 electrical equipment filled with insulating fluids. Sistema di trasmissione Brasile TSN Lines 1181 km Substations 6 Total reactors 40 Reactors with corrosive sulfur 37 (92,5%) Total failed reactors 15 (37,5%) Novatrans Lines 1278 km Substations 6 Total reactors 36 Reactors with corrosive sulfur 13 (36,11%) Total failed reactors (-) 2005 Discovery of DBDS. Sea Marconi, first in the