Scenario

Hydro power plant

Nameplate data of transformer:

Transformer: power transformer
Year: 1948
Power [MVA]: 33
Voltage [KV]: 225
Oil mass [Kg]: 74.000 

Solution Sea Marconi

Solution: Dehydration treatment performed on-load (transformer fully load during the treatment)

Before the treatment

After the treatment

After 6 months

Oil temp. [°C] 15 63 35
Dissolved water [mg/Kg] IEC 60814 28 8 14
Saturation pecentage 62% 3% 13,94%
Water inside the paper using the equilibrium curve > 10% (*) 3,9%
Insulating condition IEC 60422 Extremely wet (*) Moderately wet
Breakdown voltagea [KV] IEC 60156 39,8 > 75 > 75