Removal of corrosive sulfur from by-products of sulfur combustion (C3) Uruguay 2010

Scenario Uruguayan utility October 2012: Failure 2 weeks after a reclaim treatment with fuller earth (performed by a local operator). Nameplate data of the transformer: Transformer: grid transformer with OLTC Namufact.: xxx Year: 1977 Power [MVA]: 425 Voltage [KV]: 500 Oil mass [Kg]: 58.000 Oil type: YPF65 paraffinic oil not inhibited Segni di arco elettrico sui contatti del selettore Analysis and diagnosis (by the holder)
Lee mas

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2013

Scenario Nameplate data of transformer: Transformer: grid transformer Manufact: xxx Year: 1957 Power [MVA]: 50 Voltage [KV]: 225 Oil Mass [Kg]: 38.000 Oil type: blended mineral oil Trasformatore affetto da PCB e presenza di composti corrosivi solforati Solution Selective depolarization treatment (Chedcos) in order to remove corrosive sulfur compounds and dehalogenation treatment (CDP Process®) in order to remove the PCBs from oil and transformer. The treatment was
Lee mas

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2012

Scenario Hydro power plant with 3 GSU transformers Nameplate data of the transformer: Manufact: xxx Year: 1965 Power [MVA]: 80 Voltage [KV]: 220 Oil mass [Kg]: 35.000 Oil type: naphthenic blended Solution Selective deplarization treatment (Chedcos) in order to remove the corrosive sulfur compounds and dehalogenation treatments (CDP Process®) in order to remove the PCBs from the oil and the transformers. the tratments were performed
Lee mas

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2010

Scenario Steel Factory: 8 Equipment Nameplate data of the transformers: Namufact: xxx Year: 1973 Power [MVA]: 85 Voltage [KV]: 63 Oil mass [Kg]: 18.150 Oil type: naphthenic blended Fingerprint dell’olio. Si evidenzia la presenza di composti solforati responsabili della corrosività dell’olio Solution Selective depolarization treatment (Chedcos) in order to remove the corrosive sulfur compounds and dehalogenation treatments (CDP Process®) in order to remove the PCBs from the oils
Lee mas

Francia 2012 Eliminación de azufre corrosivo sin DBDS (C2)

Escenario El tratamiento clásico con tierra Fuller resulta totalmente ineficaz contra el azufre corrosivo. Características técnicas del transformador: Fabricante: xxx Año: 1969 Potencia [MVA]: **14** Tensión [KV]: **63** Masa de aceite [Kg]: **4.200** Tipo de aceite: Esso Univol 54 Fingerprint dell’olio. Presenza di composti solforati NON DBDS El tratamiento con tierras Fuller (NO de Sea Marconi) no ha producido ningún
Lee mas

Remoción de azufre corrosivo no-DBDS (C2) – Italia 2011

Escenario Central térmica con 8 transformadores elevadores Características técnicas de los transformadores : Fabricante: xxx Potencia [MVA]: 370 Tensión [KV]: 400 Masa de aceite [Kg]: 58.000 Tipo de aceite: aceite blendado Los análisis y diagnósticos de 2011 mostraron: Azufre total = 5700 mg/Kg TCS (Total Corrosive Sulfur) = 104 mg/Kg (equivalente a DBDS) Prueba CCD = corrosivo DBTP (dibenzotiofeno) =
Lee mas

Remoción de azufre corrosivo no DBDS (C2) – Medio Oriente 2009

Scenario Thermal power plant with 8 GSU transformers Nameplate data of the transformers: Power [MVA]: 175 Voltage [KV]: 400 Oil type: naphthenic oil C2 – Corrosione NON legata a DBDS Step 1 The diagnosis in the 2009 showed: Total sulfur = 200 mg/Kg TCS (Total Corrosive Sulfur) = 157 mg/Kg (DBDS eq.) CCD Test = corrosive IFT = 19 mN/m DBTP
Lee mas

Remoción de azufre corrosivo con DBDS (C1) – Qatar 2012

Scenario Company in the chemical business, 4 GSU transformer Nameplate data of the transformer: Manufatc: xxx Year: 2000 Power [MVA]: 47 Voltage [KV]: 34 Oil mass [Kg]: 12.000 Oil type: naftenico Solution Solution: Selective depolarization treatment (Chedcos) performed on-ste and on-load (transformer in service e fully load during the treatment). The treatment has guaranteed DBDS < 10 mg/kg. Before treatment After treatment DBDS [mg/Kg] 125
Lee mas

Remoción de azufre corrosivo con DBDS (C1) – Chile 2012

Scenario Primary substation with 3 Grid transformer and 2 shunt reactors Nameplate data of the transformer: Manufact: xxx Year: 1998 Power [MVA]: 250 Voltage [KV]: 345 Oil mass [Kg]: 118.000 Oil type: naphthenic Analitical and diagnostic results The analysis and subsequent diagnosis performed by Sea Marconi on the machines of the customer showed a clear presence of DBDS Profilo di distillazione
Lee mas

Remoción de azufre corrosivo con DBDS (C1) – Italia 2005

Scenario 4 GSU transformer at thermal power plant Nameplate data of the transformers: Manufact: xxx Year: 1997 Power [MVA]: 192 Voltage [KV]: 400 Oil mass [Kg]: 58.000 Oil type: naphthenic May 2005 The analysis and subsequent diagnosis performed by Sea Marconi on the equipment of the customer showed: Index of corrosiveness =1 (max level) ASTM b 48H= 4C Overall Health index: 0.52
Lee mas