Identificada nueva problemática (patología): C5, corrosión de los contactos de plata originada por compuestos de azufre totales

Sea Marconi es uno de los principales expertos mundiales en fenómenos de corrosión, habiendo descubierto en 2005 el DBDS como la principal causa de fallas relacionadas con el azufre corrosivo (C1). En los últimos 2 años, Sea Marconi ha brindado asistencia y ha estado directamente involucrada en varios casos de fallas relacionadas con fenómenos de corrosión en los contactos de

Lee mas

4
nov
2022

The treatment of corrosive sulfur on giant transformers in Saudi Arabia is now in Transformer Magazine

The technical-scientific article describing the corrosive sulfur depolarization treatment (DBDS removal) on giant transformers that Sea Marconi is carrying out in Saudi Arabia has seen the publication (October 2022) in the main sector magazine, Transformer Magazine. The article is entitled: "On-load integrated treatment of giant power transformers in a severe scenario". The article, subjected to careful technical review by Transformer
Lee mas
11
ago
2015

EDP Portugal califica Sea Marconi gracias al tratamiento contra el azufre corrosivo

Sea Marconi ha intervenido recientemente en el norte de Portugal para tratar un transformador en una central hidroeléctrica de propiedad de la empresa EDP (Energías de Portugal), uno de los mayores productores de energía en Europa así como uno de los grupos industriales más importantes de Portugal. Los brillantes resultados de la actividad han propiciado que Sea Marconi obtuviese la
Lee mas
27
sep
2013

Se terminó con exito la despolarización de azufre corrosivo en el Desierto de Atacama en Chile

Se ha completado satisfactoriamente una de las misiones más extremas realizadas por Sea Marconi: el tratamiento de 6 transformadores cerca del Desierto de Atacama en Chile, el lugar más seco del planeta, a 3.000 m de altitud, con una diferencia térmica entre el día y la noche de más de 30 grados C. Nuestros técnicos operativos han sido capaces de adaptarse
Lee mas

Remoción de azufre corrosivo con DBDS (C1) – Región del Pacífico 2012

Scenario Company involved in production of primary aluminum with 8 rectifiers transformers Nameplate data of the transformers: Transformer: rectifier, ODAF with membrane Manufact: xxx Year: 1998 Power [MVA]: 93,4 Voltage [KV]: 66 Oil mass [Kg]: 27.200 Oil type: naphthenic Step 1 First failure with discharges of high energy (D2) Step 2 Post failure analysis, oil fingerprint with identification ant quantification of
Lee mas

Remoción de azufre corrosivo con DBDS (C1) – Qatar 2012

Scenario Company in the chemical business, 4 GSU transformer Nameplate data of the transformer: Manufatc: xxx Year: 2000 Power [MVA]: 47 Voltage [KV]: 34 Oil mass [Kg]: 12.000 Oil type: naftenico Solution Solution: Selective depolarization treatment (Chedcos) performed on-ste and on-load (transformer in service e fully load during the treatment). The treatment has guaranteed DBDS < 10 mg/kg. Before treatment After treatment DBDS [mg/Kg] 125
Lee mas

Remoción de azufre corrosivo con DBDS (C1) – Chile 2012

Scenario Primary substation with 3 Grid transformer and 2 shunt reactors Nameplate data of the transformer: Manufact: xxx Year: 1998 Power [MVA]: 250 Voltage [KV]: 345 Oil mass [Kg]: 118.000 Oil type: naphthenic Analitical and diagnostic results The analysis and subsequent diagnosis performed by Sea Marconi on the machines of the customer showed a clear presence of DBDS Profilo di distillazione
Lee mas

Remoción de azufre corrosivo con DBDS (C1) – Italia 2005

Scenario 4 GSU transformer at thermal power plant Nameplate data of the transformers: Manufact: xxx Year: 1997 Power [MVA]: 192 Voltage [KV]: 400 Oil mass [Kg]: 58.000 Oil type: naphthenic May 2005 The analysis and subsequent diagnosis performed by Sea Marconi on the equipment of the customer showed: Index of corrosiveness =1 (max level) ASTM b 48H= 4C Overall Health index: 0.52
Lee mas

Eliminación de azufre corrosivo con DBDS (C1) – Italia 2009-2014

Scenario Company involved in energy transmission (36 transformers) Nameplate data of transformers: Power max [MVA]: 528 Voltage max [KV]: 400 Oil mass [Kg]: 96.900 each DBDS max [mg/Kg]: 185 DBDS target [mg/Kg]: <5 2009-2013 Solution: Selective depolarization treatments by Sea Marconi in order to remove corrosive sulfur compounds from the oils.

Remoción de azufre corrosivo con DBDS (C1) – Brazil 2005

Scenario Brazilian energy transmission network of TSN e Novatrans with 76 electrical equipment filled with insulating fluids. Sistema di trasmissione Brasile TSN Lines 1181 km Substations 6 Total reactors 40 Reactors with corrosive sulfur 37 (92,5%) Total failed reactors 15 (37,5%) Novatrans Lines 1278 km Substations 6 Total reactors 36 Reactors with corrosive sulfur 13 (36,11%) Total failed reactors (-) 2005 Discovery of DBDS. Sea Marconi, first in the