Removal of corrosion from dissolved metals (C4) and sludge Italy 2003

Scenario Hydro power plant Nameplate data of transformer: Transformer: GSU transformer Power [MVA]: 30 Voltage [KV]: 130 Oil mass [Kg]: 58.000 Oil type: paraffinic Before the treatment Cu [mg/Kg] 43 TAN [mg KOH/g] 0,213 Color 3 DF 1,268 Solution Sea Marconi Solution: Selective Depolarization treatment (Chedcos) performed on-load (transformer fully load during the treatment) Selective depolarization treatment: Chedcos Before the treatment After the
Lee mas

Remoción de azufre corrosivo no-DBDS (C2) – Italia 2011

Escenario Central térmica con 8 transformadores elevadores Características técnicas de los transformadores : Fabricante: xxx Potencia [MVA]: 370 Tensión [KV]: 400 Masa de aceite [Kg]: 58.000 Tipo de aceite: aceite blendado Los análisis y diagnósticos de 2011 mostraron: Azufre total = 5700 mg/Kg TCS (Total Corrosive Sulfur) = 104 mg/Kg (equivalente a DBDS) Prueba CCD = corrosivo DBTP (dibenzotiofeno) =
Lee mas

Remoción de azufre corrosivo con DBDS (C1) – Italia 2005

Scenario 4 GSU transformer at thermal power plant Nameplate data of the transformers: Manufact: xxx Year: 1997 Power [MVA]: 192 Voltage [KV]: 400 Oil mass [Kg]: 58.000 Oil type: naphthenic May 2005 The analysis and subsequent diagnosis performed by Sea Marconi on the equipment of the customer showed: Index of corrosiveness =1 (max level) ASTM b 48H= 4C Overall Health index: 0.52
Lee mas

Eliminación de azufre corrosivo con DBDS (C1) – Italia 2009-2014

Scenario Company involved in energy transmission (36 transformers) Nameplate data of transformers: Power max [MVA]: 528 Voltage max [KV]: 400 Oil mass [Kg]: 96.900 each DBDS max [mg/Kg]: 185 DBDS target [mg/Kg]: <5 2009-2013 Solution: Selective depolarization treatments by Sea Marconi in order to remove corrosive sulfur compounds from the oils.