Nouveau problème identifié (pathologie) : C5 – Corrosion des contacts en argent due à des composés soufrés totaux

Sea Marconi est l’un des principaux experts mondiaux sur les phénomènes de corrosion, ayant découvert le DBDS en 2005 comme principale cause des défaillances liées au soufre corrosif (C1). Au cours des 2 dernières années, Sea Marconi a apporté son assistance et a été directement impliqué dans plusieurs cas de défaillances liées aux phénomènes de corrosion sur les contacts en

En savoir plus

4
nov.
2022

The treatment of corrosive sulfur on giant transformers in Saudi Arabia is now in Transformer Magazine

The technical-scientific article describing the corrosive sulfur depolarization treatment (DBDS removal) on giant transformers that Sea Marconi is carrying out in Saudi Arabia has seen the publication (October 2022) in the main sector magazine, Transformer Magazine. The article is entitled: "On-load integrated treatment of giant power transformers in a severe scenario". The article, subjected to careful technical review by Transformer
En savoir plus
11
août
2015

EDP Portugal qualifie Sea Marconi grâce au traitement contre le soufre corrosif

Sea Marconi a été invité récemment à débattre sur le thème du traitement d’un transformateur dans une centrale de production hydroélectrique dans le Nord du Portugal appartenant à EDP (Energias de Portugal), un des plus grands producteurs d’énergie en Europe et un des plus importants groupes industriels du Portugal. Les brillants résultats de l’activité ont permis à Sea Marconi d’obtenir
En savoir plus
27
sept.
2013

La Dépolarisation du Soufre Corrosif dans le désert la d’Atacama au Chili s’est conclue avec succès

Une de missions le plus “extrêmes” conduites par Sea Marconi s’est conclue avec succès: le traitement de 6 transformateurs auprès du désert d’Atacama au Chili, le lieu plus sec de la planète, à 3000 m d’altitude au-dessus du niveau de la mer, avec une amplitude thermique entre le jour et la nuit de plus de 30° C. Nos techniciens opérationnels ont
En savoir plus

Élimination du soufre corrosif avec DBDS (C1) région Pacifique 2012

Scenario Company involved in production of primary aluminum with 8 rectifiers transformers Nameplate data of the transformers: Transformer: rectifier, ODAF with membrane Manufacturer: xxx Year: 1998 Power [MVA]: 93,4 Voltage [KV]: 66 Oil mass [Kg]: 27.200 Oil type: naphthenic Step 1 First failure with discharges of high energy (D2) Step 2 Post failure analysis, oil fingerprint with identification ant quantification of
En savoir plus

Élimination du soufre corrosif avec DBDS Qatar 2012

Scenario Company in the chemical business, 4 GSU transformer Nameplate data of the transformer: Manufacturer: xxx Year: 2000 Power [MVA]: 47 Voltage [KV]: 34 Oil mass [Kg]: 12.000 Oil type: naftenico Solution Solution: Selective depolarization treatment (Chedcos) performed on-ste and on-load (transformer in service e fully load during the treatment). The treatment has guaranteed DBDS < 10 mg/kg. Before treatment After treatment DBDS [mg/Kg] 125
En savoir plus

Élimination du soufre corrosif avec DBDS (C1) Chili 2012

Scenario Primary substation with 3 Grid transformer and 2 shunt reactors Nameplate data of the transformer: Manufact: xxx Year: 1998 Power [MVA]: 250 Voltage [KV]: 345 Oil mass [Kg]: 118.000 Oil type: naphthenic Analitical and diagnostic results The analysis and subsequent diagnosis performed by Sea Marconi on the machines of the customer showed a clear presence of DBDS Profilo di distillazione
En savoir plus

Élimination du soufre corrosif avec DBDS (C1) Italie 2005

Scenario 4 GSU transformer at thermal power plant Nameplate data of the transformers: Manufacturer: xxx Year: 1997 Power [MVA]: 192 Voltage [KV]: 400 Oil mass [Kg]: 58.000 Oil type: naphthenic May 2005 The analysis and subsequent diagnosis performed by Sea Marconi on the equipment of the customer showed: Index of corrosiveness =1 (max level) ASTM b 48H= 4C Overall Health index: 0.52
En savoir plus

Élimination du soufre corrosif avec DBDS (C1) Italie 2009-2014

Scenario Company involved in energy transmission (36 transformers) Nameplate data of transformers: Power max [MVA]: 528 Voltage max [KV]: 400 Oil mass [Kg]: 96.900 each DBDS max [mg/Kg]: 185 DBDS target [mg/Kg]: <5 2009-2013 Solution: Selective depolarization treatments by Sea Marconi in order to remove corrosive sulfur compounds from the oils.

Élimination du soufre corrosif avec DBDS (C1) Brésil 2005

Scenario Brazilian energy transmission network of TSN e Novatrans with 76 electrical equipment filled with insulating fluids. Sistema di trasmissione Brasile TSN Lines 1181 km Substations 6 Total reactors 40 Reactors with corrosive sulfur 37 (92,5%) Total failed reactors 15 (37,5%) Novatrans Lines 1278 km Substations 6 Total reactors 36 Reactors with corrosive sulfur 13 (36,11%) Total failed reactors (-) 2005 Discovery of DBDS. Sea Marconi, first in the
En savoir plus