TAESA Brazil buys its second Sea Marconi system to combat corrosive sulphur

Recalling Sea Marconi’s most important activities in 2014, we don’t want to exclude the delivery of an oil treatment system, model DMU 100 5000 24C, to TAESA, an important Brazilian utility. We are extremely proud of this order, because TAESA already purchased one of our systems in 2009 (read article). Given their high level of satisfaction, in terms of both the
Leia mais

PCBs e corrosão C2 e C4, logística extrema – França 2013

Scenario Hydro Power Plant The transformer is located near a river dam with extreme logistical and environmental constraints. The option of changing the oil was discarded immediately because of the enormous difficulties in handling (see. Photo) around the transformer. At the same time the fuller earth techniques would not solve the functional criticalities of the system “oil – transformer”. Nameplate
Leia mais

Removal of corrosion from dissolved metals (C4) and sludge Italy 2003

Scenario Hydro power plant Nameplate data of transformer: Transformer: GSU transformer Power [MVA]: 30 Voltage [KV]: 130 Oil mass [Kg]: 58.000 Oil type: paraffinic Before the treatment Cu [mg/Kg] 43 TAN [mg KOH/g] 0,213 Color 3 DF 1,268 Solution Sea Marconi Solution: Selective Depolarization treatment (Chedcos) performed on-load (transformer fully load during the treatment) Selective depolarization treatment: Chedcos Before the treatment After the
Leia mais

Removal of corrosive sulfur from by-products of sulfur combustion (C3) Uruguay 2010

Scenario Uruguayan utility October 2012: Failure 2 weeks after a reclaim treatment with fuller earth (performed by a local operator). Nameplate data of the transformer: Transformer: grid transformer with OLTC Namufact.: xxx Year: 1977 Power [MVA]: 425 Voltage [KV]: 500 Oil mass [Kg]: 58.000 Oil type: YPF65 paraffinic oil not inhibited Segni di arco elettrico sui contatti del selettore Analysis and diagnosis (by the holder)
Leia mais

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2013

Scenario Nameplate data of transformer: Transformer: grid transformer Manufact: xxx Year: 1957 Power [MVA]: 50 Voltage [KV]: 225 Oil Mass [Kg]: 38.000 Oil type: blended mineral oil Trasformatore affetto da PCB e presenza di composti corrosivi solforati Solution Selective depolarization treatment (Chedcos) in order to remove corrosive sulfur compounds and dehalogenation treatment (CDP Process®) in order to remove the PCBs from oil and transformer. The treatment was
Leia mais

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2012

Scenario Hydro power plant with 3 GSU transformers Nameplate data of the transformer: Manufact: xxx Year: 1965 Power [MVA]: 80 Voltage [KV]: 220 Oil mass [Kg]: 35.000 Oil type: naphthenic blended Solution Selective deplarization treatment (Chedcos) in order to remove the corrosive sulfur compounds and dehalogenation treatments (CDP Process®) in order to remove the PCBs from the oil and the transformers. the tratments were performed
Leia mais

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2010

Scenario Steel Factory: 8 Equipment Nameplate data of the transformers: Namufact: xxx Year: 1973 Power [MVA]: 85 Voltage [KV]: 63 Oil mass [Kg]: 18.150 Oil type: naphthenic blended Fingerprint dell’olio. Si evidenzia la presenza di composti solforati responsabili della corrosività dell’olio Solution Selective depolarization treatment (Chedcos) in order to remove the corrosive sulfur compounds and dehalogenation treatments (CDP Process®) in order to remove the PCBs from the oils
Leia mais

Francia 2012 Rimozione zolfo corrosivo senza DBDS (C2)

Scenario Il classico trattamento con terre follari si dimostra totalmente inefficace contro lo zolfo corrosivo Caratteristiche tecniche del trasformatore: Costruttore: xxx Anno: 1969 Potenza [MVA]: 14 Tensione [KV]: 63 Massa olio [Kg]: 4.200 Tipo di olio: Esso Univol 54 Fingerprint dell’olio. Presenza di composti solforati NON DBDS Il trattamento con terre follari (NON da Sea Marconi) non ha prodotto alcun risultato
Leia mais

Remoção de enxofre corrosivo não-DBDS (C2) – Itália 2011

Cenário Central térmica com 8 transformadores elevadores Características técnicas dos transformadores : Fabricante: xxx Potência [MVA]: 370 Tensão [KV]: 400 Massa de óleo [Kg]: 58.000 Tipo de óleo: óleo blendado As análises e diagnósticos de 2011 destacaram: Enxofre total = 5700 mg/Kg TCS (Total Corrosive Sulfur) = 104 mg/Kg (equivalente a DBDS) Teste CCD = corrosivo DBTP (dibenzotiofeno) = 42
Leia mais

Remoção de enxofre corrosivo não-DBDS (C2) – Oriente Médio 2009

Scenario Thermal power plant with 8 GSU transformers Nameplate data of the transformers: Power [MVA]: 175 Voltage [KV]: 400 Oil type: naphthenic oil C2 – Corrosione NON legata a DBDS Step 1 The diagnosis in the 2009 showed: Total sulfur = 200 mg/Kg TCS (Total Corrosive Sulfur) = 157 mg/Kg (DBDS eq.) CCD Test = corrosive IFT = 19 mN/m DBTP
Leia mais