Scenario

Company in the chemical business, 4 GSU transformer

Nameplate data of the transformer:

Manufatc: xxx
Year: 2000
Power [MVA]: 47
Voltage [KV]: 34
Oil mass [Kg]: 12.000
Oil type: naftenico

Solution

Solution: Selective depolarization treatment (Chedcos) performed on-ste and on-load (transformer in service e fully load during the treatment).

The treatment has guaranteed DBDS < 10 mg/kg.

Before treatment

After treatment

DBDS [mg/Kg] 125 < 5
H2O [mg/Kg] 7 3
TAN [mg KOH/g] < 0,095 < 0,01
DF 0,0190 0,0033

Identified Critical issues


Applied solutions

Contact us to learn more about your case