Tag: oil treatment

27
Sep
2013

The depolarisation from corrosive sulfur in the desert of Atacama in Chile has been concluded successfully

Chile depolarisation. One of the most “extreme” missions performed by Sea Marconi has been concluded successfully: the treatment of 6 transformers in the desert of Atacama in Chile, the driest place in the world, at 9,000 feet altitude with a temperature range between day and night of more than 30 °C. Our operational engineers were able to adapt to really difficult conditions such
Read more

Drying papers and transformer France 2008

Scenario Hydro power plant Nameplate data of transformer: Transformer: power transformer Year: 1948 Power [MVA]: 33 Voltage [KV]: 225 Oil mass [Kg]: 74.000  Solution Sea Marconi Solution: Dehydration treatment performed on-load (transformer fully load during the treatment) Before the treatment After the treatment After 6 months Oil temp. [°C] 15 63 35 Dissolved water [mg/Kg] IEC 60814 28 8 14 Saturation pecentage
Read more

Removal of corrosion from dissolved metals (C4) and sludge Italy 2003

Scenario Hydro power plant Nameplate data of transformer: Transformer: GSU transformer Power [MVA]: 30 Voltage [KV]: 130 Oil mass [Kg]: 58.000 Oil type: paraffinic Before the treatment Cu [mg/Kg] 43 TAN [mg KOH/g] 0,213 Color 3 DF 1,268 Solution Sea Marconi Solution: Selective Depolarization treatment (Chedcos) performed on-load (transformer fully load during the treatment) Selective depolarization treatment: Chedcos Before the treatment After the
Read more

Removal of corrosive sulfur from by-products of sulfur combustion (C3) Uruguay 2010

Scenario Uruguayan utility October 2012: Failure 2 weeks after a reclaim treatment with fuller earth (performed by a local operator). Nameplate data of the transformer: Transformer: grid transformer with OLTC Namufact.: xxx Year: 1977 Power [MVA]: 425 Voltage [KV]: 500 Oil mass [Kg]: 58.000 Oil type: YPF65 paraffinic oil not inhibited Evidence of electrical arc on the contacts of the selector Analysis and diagnosis (by
Read more

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2012

Scenario Hydro power plant with 3 GSU transformers Nameplate data of the transformer: Manufact: xxx Year: 1965 Power [MVA]: 80 Voltage [KV]: 220 Oil mass [Kg]: 35.000 Oil type: naphthenic blended Solution Selective deplarization treatment (Chedcos) in order to remove the corrosive sulfur compounds and dehalogenation treatments (CDP Process®) in order to remove the PCBs from the oil and the transformers. the tratments were performed
Read more

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2010

Scenario Steel Factory: 8 Equipment Nameplate data of the transformers: Namufact: xxx Year: 1973 Power [MVA]: 85 Voltage [KV]: 63 Oil mass [Kg]: 18.150 Oil type: naphthenic blended Oil Fingerprint. It shows the presence of sulfur compounds responsible for oil corrosivity Solution Selective depolarization treatment (Chedcos) in order to remove the corrosive sulfur compounds and dehalogenation treatments (CDP Process®) in order to remove the PCBs from the oils
Read more

France 2012 Removal of PCBs and non DBDS corrosive sulfur (C2)

Scenario Il classico trattamento con terre follari si dimostra totalmente inefficace contro lo zolfo corrosivo Caratteristiche tecniche del trasformatore: Costruttore: xxx Anno: 1969 Potenza [MVA]: 14 Tensione [KV]: 63 Massa olio [Kg]: 4.200 Tipo di olio: Esso Univol 54 Oil Fingerprint. Presence of sulfur compounds without DBDS Il trattamento con terre follari (NON da Sea Marconi) non ha prodotto alcun risultato
Read more

Removal of non-DBDS corrosive sulfur (C2) Midlle East 2009

Scenario Thermal power plant with 8 GSU transformers Nameplate data of the transformers: Power [MVA]: 175 Voltage [KV]: 400 Oil type: naphthenic oil C2 – Corrosion not caused by DBDS Step 1 The diagnosis in the 2009 showed: Total sulfur = 200 mg/Kg TCS (Total Corrosive Sulfur) = 157 mg/Kg (DBDS eq.) CCD Test = corrosive IFT = 19 mN/m DBTP
Read more

Removal of corrosive sulfur with DBDS C1 Qatar 2012

Scenario Company in the chemical business, 4 GSU transformer Nameplate data of the transformer: Manufatc: xxx Year: 2000 Power [MVA]: 47 Voltage [KV]: 34 Oil mass [Kg]: 12.000 Oil type: naftenico Solution Solution: Selective depolarization treatment (Chedcos) performed on-ste and on-load (transformer in service e fully load during the treatment). The treatment has guaranteed DBDS < 10 mg/kg. Before treatment After treatment DBDS [mg/Kg] 125
Read more

Removal of corrosive sulfur with DBDS (C1) Chile 2012

Scenario Primary substation with 3 Grid transformer and 2 shunt reactors Nameplate data of the transformer: Manufact: xxx Year: 1998 Power [MVA]: 250 Voltage [KV]: 345 Oil mass [Kg]: 118.000 Oil type: naphthenic Analitical and diagnostic results The analysis and subsequent diagnosis performed by Sea Marconi on the machines of the customer showed a clear presence of DBDS Distillation profile of
Read more