Removal of PCBs and environmental protection France 2008

Scenario Nameplate data of transformer: Transformer: GSU transformer Manufact: xxx Year: 1974 Power [MVA]: 760 Voltage [KV]: 400 Oil mass [Kg]: 55.000 Problem See analytical results of the oil before treatment (table below) Soluzione Sea Marconi Solution: Dehalogenation treatment (CDP Process®) in order to remove the PCBs from the oil and transformer. Before treatment After treatment TAN [mg KOH/g] 0,029 < 0,010 Breakdown
Read more

Removal of PCBs and environmental protection France 2004-2012

Scenario Utility – Power transformer of generation (nuclear, thermal, hydro), transmission and distribution with a total of 1.093 transformers. Namepale data of transformers: Power max [MVA]: 760 Voltage max [KV]: 400 Oil mass [Kg]: 75.000 each PCB max [mg/Kg]: 5.000 PCB target [mg/Kg]: < 20 (after 90 days) Solution Sea Marconi Solution: Dehalogenation treatment (CDP Process®) in order to remove the PCBs from oils and transformers. The treatments
Read more

Removal of PCBs and environmental protection Cyprus 1997

Scenario International Tender of the Electricity Authority of Cyprus for: “Elimination of PCBs from the insulating oil of distribution transformers”. In the 1997 Sea Marconi awarded the tender for decontaminate 520 transformers. Nameplate data of transformers: Power max [KVA]: 10-1000 Oil mass contaminated [Kg]: 94.000 PCB max [mg/Kg]: 15.000 PCB target [mg/Kg]: < 10 Solution Sea Marconi Solution: Dehalogenation treatment (CDP Process®) in order to remove
Read more

Drying papers and transformer France 2008

Scenario Hydro power plant Nameplate data of transformer: Transformer: power transformer Year: 1948 Power [MVA]: 33 Voltage [KV]: 225 Oil mass [Kg]: 74.000  Solution Sea Marconi Solution: Dehydration treatment performed on-load (transformer fully load during the treatment) Before the treatment After the treatment After 6 months Oil temp. [°C] 15 63 35 Dissolved water [mg/Kg] IEC 60814 28 8 14 Saturation pecentage
Read more

Removal of corrosion from dissolved metals (C4) and sludge Italy 2003

Scenario Hydro power plant Nameplate data of transformer: Transformer: GSU transformer Power [MVA]: 30 Voltage [KV]: 130 Oil mass [Kg]: 58.000 Oil type: paraffinic Before the treatment Cu [mg/Kg] 43 TAN [mg KOH/g] 0,213 Color 3 DF 1,268 Solution Sea Marconi Solution: Selective Depolarization treatment (Chedcos) performed on-load (transformer fully load during the treatment) Selective depolarization treatment: Chedcos Before the treatment After the
Read more

Removal of corrosive sulfur from by-products of sulfur combustion (C3) Uruguay 2010

Scenario Uruguayan utility October 2012: Failure 2 weeks after a reclaim treatment with fuller earth (performed by a local operator). Nameplate data of the transformer: Transformer: grid transformer with OLTC Namufact.: xxx Year: 1977 Power [MVA]: 425 Voltage [KV]: 500 Oil mass [Kg]: 58.000 Oil type: YPF65 paraffinic oil not inhibited Evidence of electrical arc on the contacts of the selector Analysis and diagnosis (by
Read more

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2013

Scenario Nameplate data of transformer: Transformer: grid transformer Manufact: xxx Year: 1957 Power [MVA]: 50 Voltage [KV]: 225 Oil Mass [Kg]: 38.000 Oil type: blended mineral oil Transformer contaminated by PCBs and corrosive sulfur compounds Solution Selective depolarization treatment (Chedcos) in order to remove corrosive sulfur compounds and dehalogenation treatment (CDP Process®) in order to remove the PCBs from oil and transformer. The treatment was performerd on-site
Read more

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2012

Scenario Hydro power plant with 3 GSU transformers Nameplate data of the transformer: Manufact: xxx Year: 1965 Power [MVA]: 80 Voltage [KV]: 220 Oil mass [Kg]: 35.000 Oil type: naphthenic blended Solution Selective deplarization treatment (Chedcos) in order to remove the corrosive sulfur compounds and dehalogenation treatments (CDP Process®) in order to remove the PCBs from the oil and the transformers. the tratments were performed
Read more

Removal of PCBs and non-DBDS corrosive sulfur (C2) France 2010

Scenario Steel Factory: 8 Equipment Nameplate data of the transformers: Namufact: xxx Year: 1973 Power [MVA]: 85 Voltage [KV]: 63 Oil mass [Kg]: 18.150 Oil type: naphthenic blended Oil Fingerprint. It shows the presence of sulfur compounds responsible for oil corrosivity Solution Selective depolarization treatment (Chedcos) in order to remove the corrosive sulfur compounds and dehalogenation treatments (CDP Process®) in order to remove the PCBs from the oils
Read more

France 2012 Removal of PCBs and non DBDS corrosive sulfur (C2)

Scenario Il classico trattamento con terre follari si dimostra totalmente inefficace contro lo zolfo corrosivo Caratteristiche tecniche del trasformatore: Costruttore: xxx Anno: 1969 Potenza [MVA]: 14 Tensione [KV]: 63 Massa olio [Kg]: 4.200 Tipo di olio: Esso Univol 54 Oil Fingerprint. Presence of sulfur compounds without DBDS Il trattamento con terre follari (NON da Sea Marconi) non ha prodotto alcun risultato