Removal of non-DBDS corrosive sulfur C2 Italy 2011

Scenario Thermal power plant with 8 GSU transformers Nameplate data of the transformer: Manufacturer: xxx Power [MVA]: 370 Voltage [KV]: 400 Oil mass [Kg]: 58.000 Oil type: blended oil The analysis and diagnosis of the 2011 showed: Total sulfur = 5700 mg/Kg TCS (Total Corrosive Sulfur) = 104 mg/Kg (DBDS eq.) CCD Test = corrosive DBTP (dibenzothiophene) = 42 mg/Kg Step 2
Read more

Removal of non-DBDS corrosive sulfur (C2) Midlle East 2009

Scenario Thermal power plant with 8 GSU transformers Nameplate data of the transformers: Power [MVA]: 175 Voltage [KV]: 400 Oil type: naphthenic oil C2 – Corrosion not caused by DBDS Step 1 The diagnosis in the 2009 showed: Total sulfur = 200 mg/Kg TCS (Total Corrosive Sulfur) = 157 mg/Kg (DBDS eq.) CCD Test = corrosive IFT = 19 mN/m DBTP
Read more

Removal of corrosive sulfur with DBDS (C1) Pacific region 2012

Scenario Company involved in production of primary aluminum with 8 rectifiers transformers Nameplate data of the transformers: Transformer: rectifier, ODAF with membrane Manufact: xxx Year: 1998 Power [MVA]: 93,4 Voltage [KV]: 66 Oil mass [Kg]: 27.200 Oil type: naphthenic Step 1 First failure with discharges of high energy (D2) Step 2 Post failure analysis, oil fingerprint with identification ant quantification of
Read more

Removal of corrosive sulfur with DBDS C1 Qatar 2012

Scenario Company in the chemical business, 4 GSU transformer Nameplate data of the transformer: Manufatc: xxx Year: 2000 Power [MVA]: 47 Voltage [KV]: 34 Oil mass [Kg]: 12.000 Oil type: naftenico Solution Solution: Selective depolarization treatment (Chedcos) performed on-ste and on-load (transformer in service e fully load during the treatment). The treatment has guaranteed DBDS < 10 mg/kg. Before treatment After treatment DBDS [mg/Kg] 125
Read more

Removal of corrosive sulfur with DBDS (C1) Chile 2012

Scenario Primary substation with 3 Grid transformer and 2 shunt reactors Nameplate data of the transformer: Manufact: xxx Year: 1998 Power [MVA]: 250 Voltage [KV]: 345 Oil mass [Kg]: 118.000 Oil type: naphthenic Analitical and diagnostic results The analysis and subsequent diagnosis performed by Sea Marconi on the machines of the customer showed a clear presence of DBDS Distillation profile of
Read more

Removal of corrosive sulfur with DBDS (C1) Italy 2005

Scenario 4 GSU transformer at thermal power plant Nameplate data of the transformers: Manufact: xxx Year: 1997 Power [MVA]: 192 Voltage [KV]: 400 Oil mass [Kg]: 58.000 Oil type: naphthenic May 2005 The analysis and subsequent diagnosis performed by Sea Marconi on the equipment of the customer showed: Index of corrosiveness =1 (max level) ASTM b 48H= 4C Overall Health index: 0.52
Read more

Removal of corrosive sulfur with DBDS (C1) Italy 2009-2014

Scenario Company involved in energy transmission (36 transformers) Nameplate data of transformers: Power max [MVA]: 528 Voltage max [KV]: 400 Oil mass [Kg]: 96.900 each DBDS max [mg/Kg]: 185 DBDS target [mg/Kg]: <5 2009-2013 Solution: Selective depolarization treatments by Sea Marconi in order to remove corrosive sulfur compounds from the oils.

Removal of corrosive sulfur with DBDS (C1) Brazil 2005

Scenario Brazilian energy transmission network of TSN e Novatrans with 76 electrical equipment filled with insulating fluids. Brazilian energy transmission network TSN Lines 1181 km Substations 6 Total reactors 40 Reactors with corrosive sulfur 37 (92,5%) Total failed reactors 15 (37,5%) Novatrans Lines 1278 km Substations 6 Total reactors 36 Reactors with corrosive sulfur 13 (36,11%) Total failed reactors (-) 2005 Discovery of DBDS. Sea Marconi, first in the
Read more